Paper company selects van Spall for effluent cooling project
St Regis Paper Company Ltd needed to cool their waste water to meet discharge consents at their recyled paper mill in Kent.
Four vanSpall dry air coolers were installed in parallel to cool the effluent prior to entering the activated sludge lagoon in times high ambient or high effluent remperatures.
Due to the potential of suspended solids in the effluent resulting fouling of the tubes, the coolers were specified with removeable headers to facillitate cleaning
Technical Data
4off Model DVVD142489D4 Dry Air Coolers
Duty 500 kW each.Entering water temp 40C Leaving temp. 38.4C Ambient temp. 30.0C Flow rate 76.4 l/s Media: process effluent
Dimensions 7205LX2600WX3081H Tube matetrial: 304 stainless steel, Fin material Aluminium, Casing Galvanised steel